Get your ducts in a row!

Services

The Test

What we do, how we do it, and what you need to have ready.

What Is a Duct Leakage Test?

A duct leakage test measures how much air escapes from a ducted system under pressure. The test pressurizes the system to 25 Pa (0.1″ w.g.) with all registers sealed, then measures the airflow required to maintain that pressure, which equals the total leakage in CFM. Given the conditioned floor area in square feet, that total leakage number can be compared to the code threshold.

Who Needs a Test?

NY: 2025 ECCCNYS R403.3.7, effective 12/31/2025 · CT: 2022 CT State Building Code (2021 IECC) R403.3.5, effective 10/1/2022

✓ Yes: Test Required

  • New homes: all residential ductwork
  • Additions: any added ductwork
  • New or replaced duct systems in an existing home under permit
  • Ducts inside the thermal envelope still get tested, with a looser limit
  • Test at rough-in (before drywall) or post-construction

✗ No: Exempt (Rare)

  • Ventilation-only ductwork (e.g. HRV/ERV) not integrated with the heating or cooling system
  • NY only: ≤ 10 ft of ductwork outside the equipment, no building-cavity plenums, and all ducts and units within conditioned space

CT alterations and repairs follow IECC Chapter 5. Confirm with your building department.

Allowable Leakage

New York · Table R403.3.8 — Maximum Allowable Duct Leakage2025 ECCCNYS · eff. 12/31/2025
Conditioned floor areaOver 1,000 SF1,000 SF or less
Leakage units[ CFM25 / 100 SF ][ CFM25 ]
Returns<3 Returns3+ ReturnsAny
Ducts outside conditioned spaceEquipment not installed3430
All components installed4640
Ducts inside conditioned spaceEquipment not installed6860
All components installed81280
Connecticut · IECC R403.3.6 — Maximum Allowable Duct LeakageCFM25 per 100 SF of conditioned floor area
Ducts outside conditioned spaceRough-in test — air handler NOT installed3.0
Rough-in test — air handler installed4.0
Post-construction test (final)4.0
Ducts inside conditioned spaceAll ducts AND the air handler entirely within the building thermal envelope8.0

Our Equipment

Calibrated Fan

Retrotec US340X: used to pressurize the duct system and measure total leakage airflow in CFM.

Digital Manometer

Retrotec DM32X: measures the pressure differential across the duct system at 25 Pa.

Vent Caps & Tape

Used to seal all supply and return registers before pressurization.

Laser Tape Measure

Used to measure the conditioned floor area in square feet.

Common Leak Locations

  1. Boots
  2. Take-offs
  3. The air handler cabinet

Ensure these areas are sealed with mastic tape or duct seal.

Test Procedure: Step by Step

  1. 1

    Schedule

    Request a Test online or call/text to schedule.

  2. 2

    Test

    On site, with your tech, in a 2-hour window.

    1. A

      Seal Registers

      We seal all supply and return registers with vent caps or tape, leaving every opening in the duct system sealed except the connection point for the Duct Blaster.

    2. B

      Connect the Duct Blaster and Static Pressure Probe

      We connect the Duct Blaster fan at a return register or the air handler cabinet, and place a static pressure probe in the supply side so the manometer reads the pressure across the duct system.

    3. C

      Pressurize to 25 Pa

      We adjust the fan until the duct system holds exactly 25 Pa (0.1" w.g.).

    4. D

      Record Leakage

      The airflow through the fan at 25 Pa is the total duct leakage (CFM25). We divide it by the conditioned floor area to get CFM25 per 100 sf.

    5. E

      Pass/Fail Determination

      We compare the result to the applicable limit in the New York or Connecticut table above.

  3. 3

    Report Issued Same Day

    We email you the signed test report the same day. It includes all readings, the applicable threshold, test methodology (ANSI/RESNET/ICC 380), and a clear pass/fail determination.

What to Have Ready Before We Arrive

  • ✓ Ductwork fully installed and connected
  • ✓ Air handler installed or removed, either is fine, but affects which leakage threshold applies
  • ✓ Access to the duct system (return register opening or air handler cabinet)
  • ✓ Your tech on site: we strongly encourage your technician to be present to seal minor leaks and avoid a re-test

If the System Fails

A failure is not a crisis. If the measured leakage exceeds the code threshold, the contractor has two options:

  • AIf there is significant leakage, seal the ductwork and schedule a re-test on a separate day.
  • BSpend the remainder of the two-hour test block sealing, then pay for additional 30-minute blocks so our technician can wait and keep testing until the system passes. Each additional 30-minute block is $40, and staying to pass on the same visit means you skip the separate $500 re-test fee entirely.

Re-test on the same project: $500, scheduled for a separate day once you've sealed the leaks. We issue the new signed report the same day we come back to re-test.

Key Code References

  • ECCCNYS R403.3.7: Duct System Testing (2025 edition)
  • ECCCNYS R403.3.8: Duct System Leakage (thresholds)
  • ECCCNYS R503.1.2: Existing Buildings retrofit trigger
  • 2021 IECC R403.3.5: Duct Testing (2022 CT State Building Code)
  • 2021 IECC R403.3.6: Duct Leakage (CT thresholds)
  • ANSI/RESNET/ICC 380: Required test methodology
  • ASTM E1554: Alternative test standard

Testing is performed by a technician certified by the Building Performance Institute (BPI) in Infiltration & Duct Leakage (IDL), the nationally recognized credential for duct leakage measurement, under licensed PE oversight.

Fast scheduling for HVAC contractors.

Rush service available.